Estimates ultimate (LRFD) and ASD wind pressures on doors and windows — components and cladding, wall Zones 4 and 5 — for low-rise enclosed or partially enclosed buildings per ASCE 7-22 Chapter 30, Part 1.

How to use this calculator
  1. Wind speed: Enter the ultimate wind speed (V) in mph from the ASCE 7-22 maps (or the ASCE Hazard Tool) for your risk category and location.
  2. Building dimensions: Input the length, width, and mean roof height (h) in feet. The low-rise method applies for h ≤ 60 ft.
  3. Exposure category: Choose B (urban/suburban), C (open terrain), or D (coastal/flat) based on surrounding terrain.
  4. Enclosure: Enclosed or partially open buildings use GCpi = ±0.18; partially enclosed (e.g., large unprotected openings on one wall) use ±0.55 per Table 26.13-1.
  5. Topographic factor (Kzt): 1.0 for flat sites; compute per ASCE Fig. 26.8-1 for hills, ridges, or escarpments.
  6. Roof slope (θ): For θ ≤ 10°, wall GCp values are reduced 10% per the Fig. 30.3-1 footnote.
  7. Ground elevation: Optional. Site elevation above sea level sets Ke per Table 26.9-1 (leave 0 for the conservative Ke = 1.0).
  8. Effective wind area: The component's tributary area (sq ft). GCp is log-interpolated between A = 10 and A = 500 sq ft.

Zones: Zone 5 is the end zone within distance 'a' of building corners; Zone 4 is the remaining wall area. The diagram in the results shows where each applies.

Outputs: Ultimate pressures are strength-level (1.0W). ASD values are 0.6 × ultimate, the level usually compared against window/door DP ratings — confirm with your product approval and AHJ. A 16 psf strength-level minimum is enforced per Section 30.2.2.

Parameters

1.0 = flat site. Typical hill/escarpment values run 1.1–1.6.
Optional. 0 = sea level (Ke = 1.0, always conservative).

Design Pressures (Net)

End Zone, a
--
Kh
--
qh
--
Ke
--
16 psf min
Zone 4 (Interior)
-- / --
psf ultimate (Pos / Neg)
ASD 0.6W: -- / -- psf
16 psf min
Zone 5 (Corners)
-- / --
psf ultimate (Pos / Neg)
ASD 0.6W: -- / -- psf
Wall elevation showing Zone 5 corner strips of width a and Zone 4 interior wall area 5 4 5 a = -- ft Zone 5 (end zone, higher suction) Zone 4 (interior wall)

An opening within distance 'a' of any building corner uses Zone 5 pressures.

Component Wind Loads

Zone 4 Total Force
-- / --
lbs ultimate (Pos / Neg)
Zone 5 Total Force
-- / --
lbs ultimate (Pos / Neg)
View Calculation Breakdown

Positive pressures act inward, negative outward (suction). Ultimate values include the 16 psf minimum of ASCE 7-22 Sec. 30.2.2 where it governs. ASD = 0.6 × ultimate.