Gable and hip roofs, 0° to 45° · h ≤ 60 ft · Figs. 30.3-2A to 30.3-2G · v2.0
Enter the wind speed, the building, the roof and the effective wind area of the component you are sizing. Results update as you type: design pressure for every roof zone at strength level and at ASD (0.6 W), a zone drawing in proportion to your plan, and a table across common effective wind areas.
Pressures follow Eq. 30.3-1, p = qh Kd [(GCp) − (GCpi)], with Kd = 0.85 and the 16 psf minimum of Sec. 30.2.2. Kh uses z = 15 ft for any height below 15 ft, in every exposure (Table 26.10-1).
| Zone | GCp | Strength (psf) | ASD, 0.6 W (psf) |
|---|
Negative acts away from the roof (uplift), positive toward it. Sizing a fastener or a product rated by allowable load? Use the ASD column.
Disclaimer: This calculator implements the ASCE 7-22 Chapter 30 components-and-cladding equations for roofs of low-rise buildings. It is a calculation aid, not a substitute for project-specific engineering by a licensed design professional, who must confirm every input, the governing code edition and local amendments.