Oasis Fire Rating Detail

Why Fire Safety in Residential Construction Matters

By Peter Tran
Project Coordinator | Oasis Engineering

Each year, residential fires in the United States cause thousands of injuries, hundreds of fatalities, and billions of dollars in property loss. The risks are especially heightened in homes constructed with wood framing, located in high-wind or hurricane zones, or utilizing gas appliances and backup batteries.

Proper fire safety design doesn’t just meet code—it saves lives. It slows the spread of fire, provides early warning, and ensures safe means of escape. At Oasis Engineering, we prioritize code-compliant, life-safety-centered designs that help protect your investment—and your family.


1. Fire-Resistant Construction

Code Reference: IRC R302 (Fire-Resistant Construction)

Exterior Walls (Distance from Property Line):

  • < 5 feet: Must be 1-hour fire-resistance-rated (tested per ASTM E119) with no openings permitted (windows/doors).
  • 5–10 feet: Fire-rated wall required, openings limited to 25% of the wall surface.
  • > 10 feet: Standard construction is permitted; fire-resistance rating not required.

Fire-Blocking:
Per IRC R302.11, fire-blocking is essential to stop hidden fire spread:

  • Required in concealed spaces between floors, stairs, wall cavities, and soffits.
  • Must be installed every 10 vertical feet and at each floor/ceiling level.
  • Acceptable materials include:
    • 2″ nominal lumber
    • ¾” plywood or OSB
    • ½” gypsum board
    • Mineral wool insulation (non-combustible)

2. Smoke & Carbon Monoxide Alarms

Code Reference: IRC R314 & R315

Smoke Alarms must be:

  • Installed inside each bedroom,
  • Outside each sleeping area (e.g., hallways),
  • On every level, including basements.
  • Hard-wired with battery backup and interconnected so all alarms sound when one is triggered.

CO (Carbon Monoxide) Alarms are required:

  • In any home with gas appliances, fireplaces, or an attached garage.
  • Install outside each sleeping area and on every floor with fuel-burning equipment.

Maintenance Tips:

  • Test alarms monthly.
  • Replace batteries annually, or as directed by the manufacturer.
  • Replace alarms entirely every 10 years.

3. Emergency Escape & Rescue Openings

Code Reference: IRC R310

All sleeping rooms and basements without direct exterior access must have Emergency Escape and Rescue Openings (EEROs). This typically means an egress-compliant window. Requirements:

  • Minimum clear opening area: 5.7 sq. ft (5.0 sq. ft at ground level)
  • Minimum opening height: 24 inches
  • Minimum opening width: 20 inches
  • Maximum sill height: 44 inches from floor
  • Must be operable from inside without tools, keys, or special knowledge

Basement Egress Windows:

  • Window wells required when window is below grade
  • Minimum horizontal area: 9 sq. ft
  • Minimum dimensions: 36″ projection and width

4. Special Fire-Sensitive Equipment & Systems

Energy Storage Systems (ESS) — NFPA 855

Battery-based storage (solar, off-grid, etc.) is regulated under NFPA 855.

  • Must maintain 3 ft of clearance from walls/ceilings unless in a UL-listed fire-rated cabinet
  • Install only in non-sleeping areas like garages, utility rooms, or exterior enclosures
  • Avoid installing batteries inside bedrooms or closets

Gas Appliances & Electrical Panels

  • In flood hazard areas, these must be installed above Base Flood Elevation (BFE) or protected using flood-resistant design (see IRC R322)

Why This Matters

Fire safety is not just a checklist item—it’s a cornerstone of resilient, sustainable residential design. Adhering to International Residential Code (IRC) requirements and NFPA standards ensures compliance, enhances occupant safety, and supports insurability and resale value.

Whether you’re building a new home, retrofitting a garage, or installing a battery backup system, fire safety must be integrated from the start. At Oasis Engineering, we design with life safety first—and that makes all the difference.